Revelations that the 120MW data centre planned for the AI Growth zone at Chapelhall will run diesel generators to assist with cooling when temperatures are above 21 degrees have been compounded by concerns over proposals for an extension at an existing site which is operating nearby. SEPA are seeking public opinion on the generators proposed for the DV1 extension, which will only have scrubbers on half of the chimneys, among other issues. We are asking people to respond to the consultation with their concern over the generators before the deadline of 14th October.

This is a summary of a story by investigative journalist Petra Matijevic in The National on 29th September.

Petra Matijevic revealed, in a story for The National, that Datavita is seeking approval to use backup generators in hot weather for non-emergency use at its so-called “green” 120-megawatt data centre– DV4– proposed at Chapelhall, North Lanarkshire. Concerns have been raised by experts over the potential lack of pollution controls. DV4 is one of four sites proposed by DataVita in Chapelhall.

‘Back-up’ generators

The diesel generators would operate in power outages, and also during hot weather, to provide extra power for cooling, when peak customer demand coincides with air temperatures above 21ºc. DataVita insists its data centres would be always powered from the grid in normal operation. But at the hyperscale data centre, which is only metres from homes in Chapelhall, hot weather will trigger the use of these generators. This is the first proposal we have seen which plans to use emergency engines during non-emergencies, although we are aware that this possibility was also raised in the planning permission for the much smaller existing data centre currently operating close to the site.

The use of diesel generators is also planned at other DataVita sites under construction, the DV1 extension and DV3 data centers, which are already under construction. DV4 is approximately 6x larger than DV1. 

See: Noise assessment for DV4. Pages pp. 9-10 refer to load support for high IT load and temperatures above 21 degrees; refers to number of generators included in load support (32 out of 48 at DV4):

See: Energy statement for DV4. Page p. 11 refers to load support:

Lack of pollution controls

Worryingly, DataVita intends to install pollution control– scrubbers– on just 6 out of 12 of the generator flues at the DV1 extension. Upgrades will take place in the next three years subject to whether “capital expenditure is approved” (DataVita). This would not breach current air quality limits on the Scottish Environmental Protection Agency (SEPA) guidelines. 

DataVita appear to be useing absolute minimum levels of technology that they need in order to pass standards of air quality. Local resident Jen Thompson, who lives 50m from the proposed hyperscale site, shared her concerns over the pollution her children could be exposed to on warmer days: “To hear that DataVita are saving money by doing less to stop the generator fumes at the DV1 site is really shocking. I’m concerned that they will be doing the same at the massive data centre that’s planned for outside our homes.”

Furthermore, an air quality consultant found that DataVita may have significantly underestimated its predictions for emissions of nitrogen dioxide during power outages, a pollutant that causes damage to health and the environment.

See: EASR permit application for DV1 to SEPA. Page p. 8 refers to 6 out of 12 generators being equipped with SCR and the rest upgraded “once additional capital expenditure is approved”:

See: Cumulative air quality impact assessment for DV4. On page 13, the table lists emission rates used in pollution modelling and show NOx emission rate resuming all generators (including at DV1 and DV13) are equipped with SCR:

Public consultation on diesel generations – please contribute

SEPA has launched a public consultation survey about the diesel generators, which closes on Wednesday 14th October. We are urging people to respond to this as soon as possible and share your concerns about the presence of diesel generators so close to homes, that they are not all going to be fitted with scrubbers to reduce emissions, and to express concern about how often they are to be switched on for testing and how SEPA can assure residents that their health will not be affected. Developers should be using best available technology and not be allowed to get away with less when human health is at risk.

DataVita already received a £300m loan from the UK and Scottish Governments to complete the DV1 extension and DV3, both of which are currently under construction. Public money is being spent on polluting data centres and they should be required to have the best possible scrubbers on all their generator flues to protect human health.

This consultation is extremely important as we believe there will be more applications like this as more data centres come to the stage of generator permitting, and SEPA could use the results to inform decision making in future.

Jen Thompson who lives 50m from where the 125MW data centre will be built said:

“It is a huge relief that the developer is going to have to do an Environmental Impact Assessment. I live metres from the site and my four kids are always outdoors and we walk everywhere. If the diesel generators are going to be operating when it’s hottest,  that’s exactly when all the kids in the community will be playing out and we will all have our windows open. And of course it will be the same day and night. The air pollution and the noise of it is a massive worry for us.

“To also hear that DataVita are saving money by doing less to stop the generator fumes at the other site which is already operating is really shocking. I’m concerned that they will be doing the same at the massive data centre that’s planned for outside our homes.”

Kat Jones said:

“It will be distressing for local residents that DataVita plan to use the absolutely minimum levels of technology that they need to in order to pass standards of air quality.

“DataVita is getting significant support from the public purse from both UK and Scottish Governments in the form of loans and loan guarantees, they should be required to have the best possible scrubbers on all their diesel generator flues to protect human health. It is a cynical move to put in the minimum they   can get away with just before the air quality standards change. And it makes it worse that they are  not proposing to upgrade the technology until around three years time for financial reasons. Human health is more important than profit.

“If DataVita are trying to get away with reducing protective measures against diesel pollution on their smaller site, we are very concerned about the site which is about six times larger and where they are proposing to run generators during usual operation in hot weather. It’s shocking that the council had screened them out of requiring an EIA and we are relieved that the Government will now be requiring them to do one. we will certainly be scrutinising it extremely carefully when it appears. “

Petra Matijevic said:

“The fact that SCR needs time before it can reduce exhaust pollution was told to me by a source but it’s not exactly an industry secret and every diesel vehicle has the same issue. This fact hasn’t been considered in pollution modelling in the AQIA.”

“AQIAs are supposed to show worst case scenarios. The DV4 one doesn’t.”

Read Petra Matijevic’s article in The National below and here.

used with permission

Pollution fears over data centres in Lanarkshire AI growth zone

29th September

By Petra Matijevic

‘GREEN” data centres in a Lanarkshire AI growth zone could run diesel generators in hot weather to meet higher power demand.

Our investigation found the developer could be understating the impact of operating backup engines, prompting concerns over fumes exposure at nearby homes.

DataVita is seeking approval to use backup generators for non-emergency use at its proposed 120-megawatt facility in Chapelhall, North Lanarkshire. The generators would expand the site’s power capacity when peak customer demand coincided with air temperatures above 21C. Up to 32 of the total 48 generators could start operating in “load support mode” to help cool computing equipment, planning documents show.

Jen Thompson, who lives 50m from the proposed site, said the potential air pollution and noise were a “massive worry” for her four children who spend time outdoors. She fears generators operating on summer days could expose local children to harmful emissions when they are playing outside or when households have their windows open.

The project, DV4, is the first Scottish hyperscale data centre proposing to cover its peak power needs with emergency generators, said Action to Protect Rural Scotland (APRS), which tracks Scottish data centre projects.

The charity, along with community and campaign groups, is concerned that the additional generator use could put local residents at risk and has urged the Scottish Government to consider the issue in its forthcoming data centre strategy. Scottish Greens called for a definition of a “green data centre” that should “exclude the use of polluting diesel generators”.

The developer said an in-depth planning application will follow and is launching an online platform for public questions to “support greater transparency and debate”. DataVita said it welcomed scrutiny, but that “constructive discussion gets harder when the playbook being used against data centres starts from a narrative and then cherry-picks facts to support it”.

SAFETY SHORTCUTS AT SMALLER SITE RAISE FEARS

TWO smaller projects, DV1 and DV3, are also planning to use load support during peak time. Both were approved earlier this year, with construction under way.

DataVita forecasts load support use of no more than 80 hours a year and insists the facilities would be “always powered from the grid in normal operation”. Data centres would use hydrotreated vegetable oil, a diesel alternative. The air quality assessment assumes generators at all three sites would be fitted with emission-reduction equipment, and suggests any deterioration of air quality at nearby homes in the event of a blackout – though none are known to have occurred – would be highly unlikely.

However, a separate generator permit documentation reveals DataVita intends to install pollution control on just half of the engines at the DV1 site, with upgrades expected in the next three years “once additional capital expenditure is approved”. Installing emission-reducing gear on only six out of 12 generators would not breach current air quality limits during emergency operation, according to the developer’s assessment for the Scottish Environmental Protection Agency (Sepa), which authorises standby generators.

Questions are now raised about what nearby residents could be exposed to at the larger DV4 site. Jen said she was “really shocked” to learn DataVita may be “saving money by doing less to stop the generator fumes at the DV1 site” and worried it might attempt the same at DV4.

APRS’s Dr Kat Jones called reducing protective measures against generator pollution at the smaller site a “cynical move”. She said: “DataVita receives significant support from the public purse from both UK and Scottish governments. They should be required to have the best possible scrubbers on all their diesel generator flues to protect human health.”

DataVita received a £300m loan to extend DV1 and build DV3. Lenders include the Scottish National Investment Bank and financing is partly guaranteed by the UK Government’s National Wealth Fund. Lanarkshire AI growth zone is also entitled to electricity cost discounts.

Review of DataVita’s pollution assessment report by an air quality consultant further suggests DataVita’s predictions for nitrogen dioxide emissions during power outages could have been significantly underestimated. The expert reviewed the study on condition of anonymity because of their work in the industry.

The pollution control on generators – selective catalytic reduction (SCR) – can take 10 minutes or more to start lowering emissions and is ineffective in short-term routine engine tests, specifically at the proposed lower loads, the consultant said. “The systems take time to warm up to reach their peak efficiency, just like your car,” they added, and warned the assessment did not take this into account.

CALLS FOR CLARITY AND TRANSPARENCY

DIANE Davidson, from Woodhall, Faskine and Palacecraig conservation group, said the community needed transparency about load support operation: “Residents need to know what that means for their air quality and health.”

Sepa opened a public consultation for generator use at DV1, inviting comments until October 14. DataVita is seeking an emergency-only operation permit and may add load support through future requests. Sepa said environmental requirements for generator use during normal or peak demand can differ from emergency use and would assess the impacts accordingly.

Kim Pratt, senior campaigner at Friends of the Earth Scotland, said DV4 has been allowed to progress “without meaningful consideration of the impacts on people and nature”, while Scottish Greens co-leader Gillian Mackay said AI data centre developers “must set out clearly what environmental impact these sites are going to have”.

Mackay added: “It is particularly concerning that the levels of pollution could be underestimated, and DataVita should provide clarity on that. This is a prime example of why robust environmental checks must be put in place by the Scottish Government for any AI hyperscale data centre.”

DataVita said: “Scotland is making decisions about data centres and AI that will shape its economy for a generation. Those decisions deserve a far better quality of debate than they’re currently getting.”

The developer indicated planning documents contained technical assumptions and said its air quality impact assessment states what it covers in plain terms and was available for anyone to inspect. It said a detailed appraisal will follow, along with an in-depth planning application.

The cfirm announced it will launch a fact-checking website to verify claims about its projects, publish media responses in full and invite public engagement. It said: “People living near our sites have every right to ask questions and to have them answered directly.”

DataVita invited APRS and the Scottish Greens, prominent critics of AI data centres developments, to visit existing facilities and discuss plans. It’s now extending the invitation to all political parties.

Hyperscale projects will be shaped by a new national strategy and have been paused until the guidance is published, for up to a year. Under a new national direction, DV4 will also be required to submit a full environmental impact assessment (EIA) before planning can proceed.

The Scottish Government said its EIA rule for developments above 50 megawatts will “ensure large data centre applications will face more stringent environmental requirements”. It recognises evidence of their environmental impact “continues to develop”.

DataVita committed to deliver up to £543m in community benefits over 15 years. The full capacity of the DV1 and DV3 has been leased to CoreWeave, a US AI cloud computing provider, under a 15-year agreement. AI growth zone is a UK-Government designation for projects able to secure 500 megawatts of power or more by 2030.