Data Centre Calculator

Use this table to see how the energy capacity of the hyperscale data centres translate into figures that are more easy to understand.

Type the capacity of the data centre into the yellow box

Capacity of the data centre MW
Same as the power for how many homes600,000
Percentage of Scotland’s peak power demand15%
Energy the data centre uses in a year4,204,800MWh
Equivalent to how many Scottish households energy use in a year1,339,108
What percentage of total households in Scotland is this the equivalent of?53%
What percentage of the whole of Scotland’s energy use in 202419%
What percentage of all wind energy production in Scotland in 2024 (onshore plus offshore)14%
CO2 emissions related to the energy generation (Kg CO2) per year744,249,600Kg CO2
CO2 emissions related to the energy generation (tonnes CO2) per year – assuming most recent carbon intensity of energy figures744,250tonnes CO2

Figures used for the calculations

Average Load factor of a data centre 80% (NESO states that the ‘fleet wide average load factor is 70%, yet this has been judged to increase to 80-85% for hyperscale facilities and data centres dealing predominately with AI.)

electricty usage of average Scottish home in a year 3140KWh

Number of households in Scotland in 2024 2,550,000

Total Energy consumption in 2024 in Scotland 21.7 TWh

Energy from all wind in Scotland (offshore and onshore) 30.1 TWh

Carbon intensity of energy (2025 figures) 0.177 kgCO2e/KWh

What’s all this about Watts?

Here’s a little rundown of Power and Energy and what the difference is and why it is important.

Data centre size is measured in units of power. This is because the limiting factor of a data centre is electrical power requirements. A data centre will always run out of power before it runs out of land due to the energy requirements for the compute and the cooling.

  • Measures of energy are important for calculating the energy costs to the consumer, or greenhouse gas emissions.
  • Measures of power are useful for specifying grid infrastructure and generation demand. 
Power

Power is measured in Watts/ Kilowatts/ Megawatts/ Gigawatts, and is an important measure so that you can gauge the transmission infrastructure and generation capacity required. It needs to be specified for the maximum power demand to avoid blackouts. A rule of thumb used by grid engineers is 1MW provides power for roughly 1000 homes.

Energy


Energy is a measure of power x time and is measured in Megawatt hours (or Kilowatt hours etc).

With a data centre the power used over time averages at about 80% capacity all day and all year round. However a
home fluctuates much more with the most power used in winter and in the evenings and the least in the summer.

This means that the energy used in 1000 homes in a year (3240MWh) is far less than 1MW x 365 x 24 (8760MWh) 

MW

To give an illustration, this is 0% of Scotland’s current peak energy demand

0%

Reference: this is based on a figure of 4000MW for peak energy demand given by NESO